"Multistand" Copper Conductor PVC Insulated Armoured Control Cable | FROM | TO | Purpose / Remark | Core Status | Length | |||||
Sr.No. | Cable Tag | Cable Size (sq mm) | Equipment | TB Location | Equipment | TB Location | Used | Balance | ||
Number | x No.of core | with wire no. | with wire no. | |||||||
CONTROL CABLE (DG # 1 SYNC PANEL TO DG # 1) | ||||||||||
1 | CC- 01 | 2.5sq mm x 4Core | D.G Sync. Panel | TB-1 / 1 -J1 | DG | + Ve / J1 | Battery Charger | 2 | 2 | 100 |
/ 2 - J2 | Engine Battery | - Ve / J2 | Out Put | |||||||
2 | CC- 02 | 2.5sq mm x 4Core | D.G. Sync. Panel | TB-1 / 4 -J11 | DG | + Ve / J11 | 24V DC | 2 | 2 | 100 |
/ 5 J12 | Engine Battery | - Ve / J12 | CONTROL SUPPLY | |||||||
FOR PROTECTION | ||||||||||
AND ANNUNCIATION | ||||||||||
3 | CC- 03- | 2.5sq mm x 14 Core x | D.G. Sync. Panel | TB-1 / 6- K51 | DG | PC-3.3 TB-1 /6 | 11 | 3 | 100 | |
/ 7 - K121 | PC 3.3-TB | PC-3.3 TB-1 /7 | ||||||||
/ 8 - K51 | PC-3.3 TB-1 /8 | |||||||||
/ 9- K123 | PC-3.3 TB-1 /9 | |||||||||
/ 10- K128 | PC-3.3 TB-1 /10 | Engine control | ||||||||
/ 11 K134 | PC-3.3 TB-1 /11 | |||||||||
/ 12 -K136 | PC-3.3 TB-1 /12 | |||||||||
/ 13 -K138 | PC-3.3 TB-1 /13 | |||||||||
/ 14- K140 | PC-3.3 TB-1 /14 | |||||||||
/ 15- K142 | PC-3.3 TB-1 /15 | |||||||||
/ 16- K146 | PC-3.3 TB-1 /16 | |||||||||
/ 17- SPARE | ||||||||||
4 | CC-04 | 2.5sq mm x 6 Core | D.G.- Sync. Panel | TB-1 / 18 - K125 | DG | PC-3.3 TB-5 /1 | ||||
/ 19-- K51 | PC 3.3-TB | PC-3.3 TB-5 /2 | Engine control | 4 | 2 | 100 | ||||
/ 20- K127 | PC-3.3 TB-5 /4 | |||||||||
/ 21- K51 | PC-3.3 TB-5/5 | |||||||||
5 | CC-05 | 2.5sq mm x 10 Core | D.G. Sync. Panel | TB-1 / 23 - K162 | DG | PC-3.3 TB-10 /1 | ||||
/ 24 - K164 | PC 3.3-TB | PC-3.3 TB-10 /3 | Engine control | 8 | 2 | 100 | ||||
/ 25 - K166 | PC-3.3 TB-10 /4 | |||||||||
/ 26 - K168 | PC-3.3 TB-10 /2 | |||||||||
/ 27 - K170 | PC-3.3 TB-10 /7 | |||||||||
/ 28 - K172 | PC-3.3 TB-10 /8 | |||||||||
/ 29 - K174 | PC-3.3 TB-10 /9 | |||||||||
/ 30 - K176 | PC-3.3 TB-10 /11 | |||||||||
6 | CC-06 | 2.5sq mm x 6 Core | D.G. Sync. Panel | TB-1 / 1 - E223 | DG | PC-3.3 TB-7 /1 | COMMON BUS SUPPLY | 4 | 2 | 100 |
/ 2 - E443 | PC 3.3-TB | PC-3.3 TB-7 /2 | TO PCC BUS P.T. | |||||||
/ 3 - E663 | PC-3.3 TB-7 /3 | |||||||||
/ 4 - E882 | PC-3.3 TB-7 /4 | |||||||||
DG- | TB-1 / 47 - K144 | DG ACOUSTIC | PB1A | |||||||
7 | CC-07 | 2.5sq mm x 4 Core | SYNC.PANEL | /48- K146 | MOUNTED ON | D.G. EMG. STOP | 2 | 2 | 100 | |
ACOUSTIC | FROM ACOUSTIC | |||||||||
8 | CC-08 | 2.5sq mm x 4Core | D.G Sync. Panel | TB-2 / 1- P | CUSTOMER'S | CUSTOMER'S | 240 V AC SUPPLY | 2 | 2 | 40 |
/ 2 - N | LDB PANEL | LDB PANEL | FOR BATTREY CHARGER | |||||||
TB- Ph & N. | AND ACOUSTIC LIGHT | |||||||||
9 | CC-09 | 2.5sq mm x 4Core | D.G. Sync. Panel | TB-2 / 4 - H47 | DG # 1 | |||||
/ 5 - H49 | ACOUSTIC | PLUG AND SOCKET | ACOUSTIC LIGHTING. | 2 | 2 | 100 | ||||
10 | CC-10 | 2.5sq mm x 6Core | DG SYNC. PANEL | TB-3 / 1 - K251 | CUSTOMER,S | CUSTOMER,S | MAINS ACB STATUS | 4 | 2 | 40 |
/2 - K 255 | PCC PANEL | DG/MAINS I/C | ||||||||
/3 - K 251 | ACB AUX, CONTACT | |||||||||
/4 - K 257 | ||||||||||
11 | CC-11 | 2.5sq mm x 12Core | DG SYNC PANEL | TB-3 / 6 - 1H551 | CUSTOMER,S | CUSTOMER,S | GRID AND D.G. ACB | 8 | 4 | 40 |
/7 - 1H552 | PCC PANEL | MAINS I/C PANEL | CLOSING /TRIPPING . | |||||||
/9 - 1K551 | ||||||||||
/10 - 1K552 | ||||||||||
/12 - 2H551 | ||||||||||
/13 - 2H552 | ||||||||||
/15 - 2K551 | ||||||||||
/16 - 2K552 | ||||||||||
12 | CC-12 | 2.5sq mm x 6Core | DG SYNC PANEL | TB-4 / 1 - ME11 | CUSTOMER,S | CUSTOMER,S | MAINS I/C SUPPLY | 4 | 2 | 40 |
/2 - ME31 | PCC PANEL | PCC PANEL | FOR SYCN. CKT | |||||||
/3 - ME51 | ||||||||||
/4 - ME70 | ||||||||||
13 | CC13 | 2.5sq mm x 6Core | DG SYNC PANEL | TB-4 / 6 - DE11 | CUSTOMER,S | CUSTOMER,S | D.G. SUPPLY | 4 | 2 | 40 |
/7 - DE31 | PCC PANEL | PCC PANEL | FOR SYCN. CKT | |||||||
/8 - DE51 | ||||||||||
/9 - DE70 | ||||||||||
4 | 2 | 40 | ||||||||
14 | CC14 | 2.5sq mm x 6Core | DG SYNC PANEL | TB-4 / 11 - BE11 | CUSTOMER,S | CUSTOMER,S | D.G. COMMON BUS SUPPLY | |||
/12 - BE31 | PCC PANEL | MAINS I/C PANEL | FOR SYCN. CKT | |||||||
/13 - BE51 | ||||||||||
/14 - BE70 | ||||||||||
15 | CC15 | 2.5sq mm x 2corex2RU | DG SYNC PANEL | TB-5 / 11 - BE11 | DG | PC-3.3 TB-9 /10 | Engine Load Sharing | 4 | 0 | 100 |
TWISTED PAIR | /12 - BE31 | PC 3.3-TB | / 7 | line | ||||||
SHIELDED | /13 - BE51 | / 11 | ||||||||
/14 - BE70 | / 8 | |||||||||
/ 9 | ||||||||||
Project Manager -MEP HT,LT ,Utilities & HVAC Power , Network , CCTV, Fire protection ,FA & PA system -Project Execution & Management with 10 years of Experience (Greenfield & Brownfield Projects) Now working in EVIO PVT LTD E-Mail: vjanarth90@gmail.com; vj.jana@hotmail.com Mobile:9440996628
Sunday, 18 May 2014
Control Cable Termination details for Generator ( Powerica)
Subscribe to:
Post Comments (Atom)
MOTIVATE ALL TO ACHIEVE
MOTIVATION Motivation is an internal state that propels individuals to engage in goal -directed behavior EXAMPLE: If you tell your kids...
-
Here are the tools or software mentioned below to use AI in Excel POWER QUERY Power query is used to convert PDF to Excel and the same is u...
-
As per IE Rules-1956 HT INSTALLATIONS At a pressure of 1000 V applied between each live conductor and earth for a period of one...
No comments:
Post a Comment