"Multistand" Copper Conductor PVC Insulated Armoured Control Cable | FROM | TO | Purpose / Remark | Core Status | Length | |||||
Sr.No. | Cable Tag | Cable Size (sq mm) | Equipment | TB Location | Equipment | TB Location | Used | Balance | ||
Number | x No.of core | with wire no. | with wire no. | |||||||
CONTROL CABLE (DG # 1 SYNC PANEL TO DG # 1) | ||||||||||
1 | CC- 01 | 2.5sq mm x 4Core | D.G Sync. Panel | TB-1 / 1 -J1 | DG | + Ve / J1 | Battery Charger | 2 | 2 | 100 |
/ 2 - J2 | Engine Battery | - Ve / J2 | Out Put | |||||||
2 | CC- 02 | 2.5sq mm x 4Core | D.G. Sync. Panel | TB-1 / 4 -J11 | DG | + Ve / J11 | 24V DC | 2 | 2 | 100 |
/ 5 J12 | Engine Battery | - Ve / J12 | CONTROL SUPPLY | |||||||
FOR PROTECTION | ||||||||||
AND ANNUNCIATION | ||||||||||
3 | CC- 03- | 2.5sq mm x 14 Core x | D.G. Sync. Panel | TB-1 / 6- K51 | DG | PC-3.3 TB-1 /6 | 11 | 3 | 100 | |
/ 7 - K121 | PC 3.3-TB | PC-3.3 TB-1 /7 | ||||||||
/ 8 - K51 | PC-3.3 TB-1 /8 | |||||||||
/ 9- K123 | PC-3.3 TB-1 /9 | |||||||||
/ 10- K128 | PC-3.3 TB-1 /10 | Engine control | ||||||||
/ 11 K134 | PC-3.3 TB-1 /11 | |||||||||
/ 12 -K136 | PC-3.3 TB-1 /12 | |||||||||
/ 13 -K138 | PC-3.3 TB-1 /13 | |||||||||
/ 14- K140 | PC-3.3 TB-1 /14 | |||||||||
/ 15- K142 | PC-3.3 TB-1 /15 | |||||||||
/ 16- K146 | PC-3.3 TB-1 /16 | |||||||||
/ 17- SPARE | ||||||||||
4 | CC-04 | 2.5sq mm x 6 Core | D.G.- Sync. Panel | TB-1 / 18 - K125 | DG | PC-3.3 TB-5 /1 | ||||
/ 19-- K51 | PC 3.3-TB | PC-3.3 TB-5 /2 | Engine control | 4 | 2 | 100 | ||||
/ 20- K127 | PC-3.3 TB-5 /4 | |||||||||
/ 21- K51 | PC-3.3 TB-5/5 | |||||||||
5 | CC-05 | 2.5sq mm x 10 Core | D.G. Sync. Panel | TB-1 / 23 - K162 | DG | PC-3.3 TB-10 /1 | ||||
/ 24 - K164 | PC 3.3-TB | PC-3.3 TB-10 /3 | Engine control | 8 | 2 | 100 | ||||
/ 25 - K166 | PC-3.3 TB-10 /4 | |||||||||
/ 26 - K168 | PC-3.3 TB-10 /2 | |||||||||
/ 27 - K170 | PC-3.3 TB-10 /7 | |||||||||
/ 28 - K172 | PC-3.3 TB-10 /8 | |||||||||
/ 29 - K174 | PC-3.3 TB-10 /9 | |||||||||
/ 30 - K176 | PC-3.3 TB-10 /11 | |||||||||
6 | CC-06 | 2.5sq mm x 6 Core | D.G. Sync. Panel | TB-1 / 1 - E223 | DG | PC-3.3 TB-7 /1 | COMMON BUS SUPPLY | 4 | 2 | 100 |
/ 2 - E443 | PC 3.3-TB | PC-3.3 TB-7 /2 | TO PCC BUS P.T. | |||||||
/ 3 - E663 | PC-3.3 TB-7 /3 | |||||||||
/ 4 - E882 | PC-3.3 TB-7 /4 | |||||||||
DG- | TB-1 / 47 - K144 | DG ACOUSTIC | PB1A | |||||||
7 | CC-07 | 2.5sq mm x 4 Core | SYNC.PANEL | /48- K146 | MOUNTED ON | D.G. EMG. STOP | 2 | 2 | 100 | |
ACOUSTIC | FROM ACOUSTIC | |||||||||
8 | CC-08 | 2.5sq mm x 4Core | D.G Sync. Panel | TB-2 / 1- P | CUSTOMER'S | CUSTOMER'S | 240 V AC SUPPLY | 2 | 2 | 40 |
/ 2 - N | LDB PANEL | LDB PANEL | FOR BATTREY CHARGER | |||||||
TB- Ph & N. | AND ACOUSTIC LIGHT | |||||||||
9 | CC-09 | 2.5sq mm x 4Core | D.G. Sync. Panel | TB-2 / 4 - H47 | DG # 1 | |||||
/ 5 - H49 | ACOUSTIC | PLUG AND SOCKET | ACOUSTIC LIGHTING. | 2 | 2 | 100 | ||||
10 | CC-10 | 2.5sq mm x 6Core | DG SYNC. PANEL | TB-3 / 1 - K251 | CUSTOMER,S | CUSTOMER,S | MAINS ACB STATUS | 4 | 2 | 40 |
/2 - K 255 | PCC PANEL | DG/MAINS I/C | ||||||||
/3 - K 251 | ACB AUX, CONTACT | |||||||||
/4 - K 257 | ||||||||||
11 | CC-11 | 2.5sq mm x 12Core | DG SYNC PANEL | TB-3 / 6 - 1H551 | CUSTOMER,S | CUSTOMER,S | GRID AND D.G. ACB | 8 | 4 | 40 |
/7 - 1H552 | PCC PANEL | MAINS I/C PANEL | CLOSING /TRIPPING . | |||||||
/9 - 1K551 | ||||||||||
/10 - 1K552 | ||||||||||
/12 - 2H551 | ||||||||||
/13 - 2H552 | ||||||||||
/15 - 2K551 | ||||||||||
/16 - 2K552 | ||||||||||
12 | CC-12 | 2.5sq mm x 6Core | DG SYNC PANEL | TB-4 / 1 - ME11 | CUSTOMER,S | CUSTOMER,S | MAINS I/C SUPPLY | 4 | 2 | 40 |
/2 - ME31 | PCC PANEL | PCC PANEL | FOR SYCN. CKT | |||||||
/3 - ME51 | ||||||||||
/4 - ME70 | ||||||||||
13 | CC13 | 2.5sq mm x 6Core | DG SYNC PANEL | TB-4 / 6 - DE11 | CUSTOMER,S | CUSTOMER,S | D.G. SUPPLY | 4 | 2 | 40 |
/7 - DE31 | PCC PANEL | PCC PANEL | FOR SYCN. CKT | |||||||
/8 - DE51 | ||||||||||
/9 - DE70 | ||||||||||
4 | 2 | 40 | ||||||||
14 | CC14 | 2.5sq mm x 6Core | DG SYNC PANEL | TB-4 / 11 - BE11 | CUSTOMER,S | CUSTOMER,S | D.G. COMMON BUS SUPPLY | |||
/12 - BE31 | PCC PANEL | MAINS I/C PANEL | FOR SYCN. CKT | |||||||
/13 - BE51 | ||||||||||
/14 - BE70 | ||||||||||
15 | CC15 | 2.5sq mm x 2corex2RU | DG SYNC PANEL | TB-5 / 11 - BE11 | DG | PC-3.3 TB-9 /10 | Engine Load Sharing | 4 | 0 | 100 |
TWISTED PAIR | /12 - BE31 | PC 3.3-TB | / 7 | line | ||||||
SHIELDED | /13 - BE51 | / 11 | ||||||||
/14 - BE70 | / 8 | |||||||||
/ 9 | ||||||||||
Project Manager -MEP HT,LT ,Utilities & HVAC Power , Network , CCTV, Fire protection ,FA & PA system -Project Execution & Management with 10 years of Experience (Greenfield & Brownfield Projects) Now working in EVIO PVT LTD E-Mail: vjanarth90@gmail.com; vj.jana@hotmail.com Mobile:9440996628
Sunday, 18 May 2014
Control Cable Termination details for Generator ( Powerica)
Subscribe to:
Post Comments (Atom)
MOTIVATE ALL TO ACHIEVE
MOTIVATION Motivation is an internal state that propels individuals to engage in goal -directed behavior EXAMPLE: If you tell your kids...
-
Here are the tools or software mentioned below to use AI in Excel POWER QUERY Power query is used to convert PDF to Excel and the same is u...
No comments:
Post a Comment