Tuesday 17 November 2020

Minimum IR values of HT & LT INSTALLATIONS


As per IE Rules-1956

HT INSTALLATIONS 

  • At a pressure of 1000 V applied between each live conductor and earth for a period of one minute the insulation resistance of HV installations shall be at least 1 Mega ohm or as specified by the Bureau of Indian Standards.
  • Medium and Low Voltage Installations- At a pressure of 500 V applied between each live conductor and earth for a period of one minute, the insulation resistance of medium and low voltage installations shall be at least 1 Mega ohm or as specified by the Bureau of Indian Standards] from time to time.

Minimum IR value for HT cables

Money Vs Parents Vs Children

MOTIVATE ALL TO ACHIEVE

MOTIVATION Motivation  is an  internal state  that propels individuals to engage in  goal -directed  behavior EXAMPLE: If you tell your kids...