Tuesday 17 November 2020

Minimum IR values of HT & LT INSTALLATIONS


As per IE Rules-1956

HT INSTALLATIONS 

  • At a pressure of 1000 V applied between each live conductor and earth for a period of one minute the insulation resistance of HV installations shall be at least 1 Mega ohm or as specified by the Bureau of Indian Standards.
  • Medium and Low Voltage Installations- At a pressure of 500 V applied between each live conductor and earth for a period of one minute, the insulation resistance of medium and low voltage installations shall be at least 1 Mega ohm or as specified by the Bureau of Indian Standards] from time to time.

No comments:

Post a Comment

MOTIVATE ALL TO ACHIEVE

MOTIVATION Motivation  is an  internal state  that propels individuals to engage in  goal -directed  behavior EXAMPLE: If you tell your kids...